Coriolis Massflowmeter. Range: min. min.0-1200 kg/h - max. 0-12000 kg/h. Output 1: 4 - 20mA with HA
Coriolis Massflowmeter
Model: TMU-S-015-201R-B-0-0-C-A-1-0-0-K / UMC4-D-2-A-2-1
Brand: Heinrichs - Kobold
[TMU-S]:
Wetted materials, Stainless steel
[015]: Meter line size, DN15 ANSI ½"
Range, min. 0-1200 kg/h - max. 0-12000 kg/h
[201R]: Process connection, ½" Class 150 RF ASME B16.5-2003
Installation length, 535 mm
[B]: Containment options, Standard containment with drain connection ½" NPT (f)
[0]: Heating / cooling, None
[0]: Connection for heating / cooling, None
[C]: Sensor configuration,Remote mount transmitter
Process temperature,-40° to 212°F, -40° to 100°C
Sensor Cable Connection, Terminal block via ½" NPT (f) IP66
[A]: Approvals, II 1/2G EEx ia IIC T6 - T2
[1]: Calibration flow, Standard, 3-point
[0]: Calibration density, None
[0]: Supplementary equipment, None
[K]: Design, Kobold
**********************************************************************
[UMC4-D]: UMC4-D-1-2-A-2-1
Mounting, Remote mount / terminal connection box, mounted
Conduit port opening,M20 x 1,5
[1]: Display / Interface board, Integral within transmitter housing, for ambient temperature up to 60°C
[2]: Power supply, 19 - 36V DC, 24V AC (±20%), 50/60Hz
[A]: Outputs
Analog output 1: 4 - 20mA with HART®
Analog output 2: 4 - 20mA
Pulse output: passive Um=30V DC
Status output: passive Um=30V DC
[2]: Approvals, II(1)2G Ex d [ia Ga] IIC T3-T4 Gb (terminal compartment Ex d), ambient to 60°C
[1]: Type of protection (signal output), Ex [ia Ga] intrinsically safe
*****************************************************************
Marca: KOBOLD |